Voltage test | 6500V as per EN 50395. |
---|---|
Max permissible operating voltage | DC 1.5kv (conductor-conductor, non earthed system) |
Nominal voltage | AC – 0.6/1 Kv, DC – 900/1.5 Kv |
Ambient Temperature | -40°C to +90°C |
---|---|
Max conductor temperature | 40°C to 120°C |
Max bending radius |
---|
5*OD(fixed installation) |
15* OD (occasional moved) |
Fire performance | IEC 60332-1-2 |
---|---|
Smoke emission | IEC 61034/ EN 50268-2 |
Halogen free | EN 50267-2-1/-2, IEC 60754-2 |
Toxicity | EN 50305, ITC – index <3 |
Ozone Resistant | EN50396 |
Weathering UV | HD 605/A1 or DIN 53367 |
Approvals | EN 50618; H1Z2Z2-K |
Solar DC Cables from PV Module to Array Junction Box |
(as per TUV Specification- EN 50618 : 2014) |
Nominal Cross-sectional (mm) | Insulation thickness Nominal in mm. | Sheath thickness Nominal in mm. | Overall Diameter in mm. | Tolerance on diameter | Tinned Copper maximum Resistance @20°C (ohms-Ω/Km) | Current Carrying capacity (Single Cable In Air) (In Amps – A) |
---|---|---|---|---|---|---|
1.5 | 0.7 | 0.8 | 4.66 | ±/-0.4 | 13.7 | 30 |
2.5 | 0.7 | 0.8 | 5.2 | ±/-0.4 | 8.21 | 41 |
4 | 0.7 | 0.8 | 5.8 | ±/-0.4 | 5.09 | 55 |
6 | 0.7 | 0.8 | 6.4 | ±/-0.4 | 3.39 | 70 |
10 | 0.7 | 0.8 | 7.3 | ±/-0.4 | 1.95 | 98 |
16 | 0.7 | 0.9 | 8.6 | ±/-0.4 | 1.24 | 132 |